I. Daily Maintenance of SPD (Surge Protective Device)
Visual Inspection
Check for cracks, scorching, or discoloration on the casing; ensure terminals are free from oxidation or looseness.
Verify labels are legible (e.g., model, voltage rating, failure indicator).
Status Indicator
If equipped with an indicator light, ensure it displays normal status (typically green = functional, red = failed).
Replace immediately if the indicator is abnormal or extinguished.
Grounding Connection Check
Performance Testing
Periodically measure let-through voltage and leakage current using a dedicated tester (replace if leakage current exceeds 1mA).
Inspect the SPD immediately after lightning strikes or major surge events.
Records and Replacement
Document inspection dates, test data, and replacement history.
Recommended service life: 5–8 years, or per manufacturer’s instructions.
Maintenance Cycle: Quarterly; additional inspections after thunderstorm seasons.
II. Daily Maintenance of MCB (Miniature Circuit Breaker)
Operational Test
Terminal Inspection
Cleaning and Heat Dissipation
Fault Analysis
Record trip frequency and causes (e.g., overload, short circuit); investigate circuit faults.
For frequent tripping, verify load compatibility (check rated current limits).
Arc Chamber Inspection
Inspect arc chute plates for integrity, absence of carbonization, or metal residue.
Replace the MCB if severe arcing traces are observed.
Maintenance Cycle: Biannually; reduce to quarterly for high-load or harsh environments.
III. Safety Precautions
De-energize and verify power is off before maintenance to prevent electric shock.
Use insulated tools; wear protective gloves/glasses.
Replace devices with identical specifications/models; avoid mixing types.
Only qualified electricians with certifications should perform operations.
IV. Common Issue Handling
SPD Failure: Replace immediately to avoid equipment exposure to surge risks.
MCB Fails to Reset: Check for short circuits or overloads; rectify faults before resetting.
Abnormal Heating: Re-tighten terminals or replace with a higher-rated device.
Regular maintenance significantly reduces electrical failure risks and extends equipment lifespan. Address identified hazards promptly and document all
actions.